| 6020 | 6030 | 6020/30 |
Insulation
Test Specifications |
Test
Voltage | 125V/250V | 250V/500V | 1000V |
Measuring
Ranges (M¥Ø) | 0
~1.999M¥Ø 1.00 ~19.99M¥Ø 10.0 ~199.9M¥Ø | 0
~19.99M¥Ø 10.0 ~199.9M¥Ø 100 ~1999M¥Ø |
(3
auto ranges) |
Accuracy |
|¡¾2%rdg
¡¾3dgt, ¡¾10%rdg (on 1000~2000M¥Ø) |
Open
Circuit Voltage | +20%
-0% of Rated Test Voltage |
Rated
Test current | 1mA
DC +20%-0% |
Short
Circuit current | 1.3mA
DC approx. |
Effect
of AC Component of Terminal Voltage | Within
¡¾10% of reading when 5µF capacitor is connected
in parallel on insulation test |
Overload
Protection | 1200V
(DC + ACp-p) for 10 seconds |
Earth Resistance
Test Specifications |
Measuring
Ranges(¥Ø) | 0
~199.9¥Ø 100 ~1999¥Ø (2 auto ranges) |
Accuracy | |¡¾2%rdg
¡¾3dgt
(at 500¥Ø auxiliary earth resistance) |
Measuring
Method | By
constant current inverter 820Hz approx. 2mA approx. |
Overload
Protection | 200V
AC for 10 seconds between measuring terminals |
Voltage
Test Specifications |
Measuring
Ranges (V) | 0
~ 199.9/100 ~ 600V (2 auto ranges) |
Accuracy | |¡¾1%rdg
¡¾4dgt |
Sensing | True
RMS |
Input
Impedance | 2M¥Ø |
Overload
Protection | 900V
AC for 1 minute |
Phase
Check Specifications |
Measuring
Range |
100
~ 600V (50Hz/60Hz)
(for checking correct or reverse
phase and open phase) |
General |
Display | 3
1/2(1999)digit large LCD |
Response
Time | Approx.
4 seconds for AC voltage and earth resistance tests
Approx. 5 seconds for insulation resistance tests. |
Withstand
Voltage | 5550V
AC for one minute |
Effect
of Drop | No
electrical and mechanical damage shall occur when the
unit is dropped from a height of 1 m onto the concrete
floor. |
Effect
of Temperature | Readings
shall not differ greater than specified below when taken
at a reference temperature of 23¨¬C and varied temperature
of 0¨¬C and 40¨¬C. AC Voltage 3% ¡¾2 dgt
insulation resistance and earth resistance 5% ¡¾2
dgt |
Operating
Temperature Range | 0-40¨¬C |
Dimensions | 130
¡¿ 238 ¡¿ 207mm (main body plus cord reel
module) 105 ¡¿ 238 ¡¿ 207mm (main body
only) |
Weight | Approx.
1.6kg (main body only) Approx. 750g (cord reel module
only) |
Power
Supply | 1.5V
LR6 alkaline battery or equivalent ¡¿ 8 (for main
body only) 1.5V LR6 alkaline battery or equivalent
¡¿ 1 (probe only) |
Safety
Standard | IEC
61010-1 CAT.III 600V Pollution Degree 2 |
Optional | 2417(Water
Proof Leakage Clamp Meter) 7093(Cord
for Extension Probe) 9080(Aluminum
Carrying Case) |